APPROVED DOCUMENTS 2010 – F, J, L
With October 2010 came many changes in the Building Regulations for England and Wales. These changes are aimed at reducing the carbon footprint and paving the way to zero-carbon buildings in the UK. Although this brings many new difficult tasks to designers and builders, it is essential for the preservation of our world. The purpose of this post is to point out the key changes to the regulations, and to provide some manufacturers and products suitable for the new regulations.
Among the changes in October were six new Approved Documents:
- AD F 2010 – Ventilation
- AD J 2010 – Combustion appliances and fuel storage systems
- AD L1A 2010 – Conservation of fuel and power: New Dwellings
- AD L1B 2010 – Conservation of fuel and power: Existing Dwellings
- AD L2A 2010 – Conservation of fuel and power: New Buildings other than Dwellings
- AD L2B 2010 – Conservation of fuel and power: Existing Buildings other than Dwellings
As well as three new compliance guides:
- The Domestic Building Services Compliance Guide 2010
- The Non-Domestic Building Services Compliance Guide 2010
- The Domestic Ventilation Compliance Guide 2010
PART F:
SUMMARY:
The key changes to Part F (Ventilation) are geared towards increasing better indoor air quality. There are new legal requirements for inspection and commissioning, operation and maintenance requirements for tenants, and higher ventilation requirements for less “draughty” dwellings. There is also reference to a new Domestic Ventilation Compliance Guide that provides information on installing, inspecting, testing and commissioning ventilation systems.
As per the legal requirements a new regulation, 20AA, has been set in place pertaining to the creation of new dwellings. 20AA states that the person responsible for the construction shall ensure the testing of the mechanical ventilation air flow rates are carried out accordingly and reported no later than 5 days to the Building Control Body after final testing. This applies to intermittent extract fans and cooker hoods too. All fixed mechanical ventilation systems in new dwellings must also be commissioned with the Building Control Body. Furthermore, the owner of the dwelling is given appropriate information and guides for maintaining and operating the ventilation system.
New ventilation requirements have been set in place to create more efficient air exchange rates in tighter air permeable dwellings (≤5m3/h/m2 @ 50 Pa). The extract ventilation rates have not changed, but background ventilation has been increased for dwellings operating intermittent extract fans and passive stack ventilation systems (Systems 1 & 2). For leakier dwellings (>5m3/h/m2 @ 50 Pa) using continuous mechanical extract (MEV), background ventilators are no longer required. A 10mm door undercut is now clarified where there is a floor finish and a 20mm undercut where there is not. Also, instead of varied duct sizing, passive stack ventilation ducts must be 125mm in diameter regardless of room type.
KEY CHANGES:
- New Domestic Ventilation Compliance Guide.
- New regulation 20AA states the person responsible for the building shall ensure the testing of mechanical ventilation airflow rates and report it to the Building Control Body no later than five days after the final test.
- All mechanical ventilation systems must be commissioned with the Building Control Body.
- New background ventilation requirements for homes tighter than 5m3/h/m2 @ 50 Pa.
- Dwellings with an air permeability >5m3/h/m2 @ 50 Pa, using MEV no longer require background ventilators.
- There is now a 10mm door undercut where there is a floor finish or a 20mm undercut where there is not.
- Passive stack ventilation duct sizes are now 125mm diameter for all rooms.
SPECIFICATION SOLUTIONS:
With the new ventilation and tighter air permeability requirements, continuous mechanical extract ventilation will become more prevalent in dwellings. Besides delivering consistent and better indoor air quality, mechanical ventilation systems can also help to reduce external noise pollution and reduce heat demand.
Mechanical Ventilation with Heat Recovery (MVHR) is a continuous mechanical ventilation system that can be used to reduce a dwelling or buildings’ heat demand. It works by extracting the humid, polluted air from wet rooms and passes it through a heat exchanger to collect the heat. The heat is then used for warming the incoming filtered fresh air. MVHR systems can recover 70-95% of heat energy that would otherwise be wasted.
- Titon’s MVHR HR Q Plus Series
- Stiebel Eltron’s LWZ Series
- Vent-Axia’s Sentinel Kinetic Series
- Vortice Heat Recovery Units
- Itho’s HRU ECO 4
- Genvex Heat Recovery Units
Continuous mechanical ventilation can be unappealing because it runs 24 hours a day. Demand Controlled Ventilation (DCV) systems can be used to reduce energy usage of a continuous mechanical ventilation system. DCV works by using CO2 and/or infrared sensors to detect the occupancy level of the building and adjusts the fan accordingly. When the building is not at peak hours, energy will be saved by reducing the ventilation. DCV is also a cost effective choice for updating older ventilation systems.
With an increase in background ventilation requirements for tighter air permeability homes running Systems 1 and 2, more trickle ventilation will be needed to comply.