Ground source heating had a very high profile as a renewable and sustainable heating source some five or six years ago but the extraordinary rise in solar PV and biomass heating, fuelled in part by government policy, has taken focus away from some of ground source’s undoubted benefits as a sustainable heating system. With recent announced increases in the Government’s RHI rate for ground source heating and the imminent introduction of a domestic/homeowner RHI, perhaps now is a good time to look at what we need to consider when specifying a ground source heating system .
With a fear of teaching grandma to suck eggs, perhaps it is a good idea to look at some of the basic principles of ground source energy and how it works first. Ground source energy is sometimes called geothermal energy, but the source of this energy is definitely not the earth. Every square metre of earth in northern Europe receives about 800 W/m2 of solar radiation, about 13W/m2 of energy from rain and from the earths core below 300m only 0.06W/m2. True geothermal energy comes from deeper than 400m, often kilometres down and beyond the discussion of this article. From depths below 15m the ground (in the UK) is a constant temperature of 10 degrees C, corresponding to the average annual air temperature above. From ground level to 15m the temperature is influenced by the seasonal air temperature above. In the winter close to the surface the ground temperature is colder and in the summer the ground temperature is warmer. Strangely, the temperature from 5-15m is slightly reversed, being marginally cooler in the summer and warmer in the winter. This is down to the variations in the surface temperature which can take up to sixth months to move through the earth and demonstrates that the earth can be a good thermal store in many conditions. I will show how this can be used to our advantage later.

REHAU Ground source solutions
Heating your house to 10 degrees C is not going to make you very comfortable though so we need to boost this temperature to a level that is useful in keeping us warm. We do this with a heatpump; a heatpump is just like your fridge, which is cold on the outside because it is dumping heat out the back. If you put your hand around the back of your fridge you will feel it is quite warm. We have three separate but very much interconnected circuits. The ground loop circuit has a water glycol mix coming out of the heat pump at freezing or just below. The ground loops heat this mixture up to a temperature of about 5 degrees C and this heat is transferred via a plate heat exchanger to a refrigerant which will turn into a gas at the corresponding temperature. The gas can then be compressed with a pump and the increase in pressure results in an increase in temperature. A second plate heat exchanger transfers the energy into a heating circuit and an expansion value takes the refrigerant back to the original pressure and low temperature.
These three circuits are inextricably linked and the higher the temperature of the heating circuit, the harder the heatpump has to work. Ground source heating is not no energy’ but a ‘low energy’ system and the amount of energy required to run the system is measured in the COP or coefficient of performance of the system. For a system returning a ground circuit temperature of 5 degrees C and a heating circuit flow temperature of 55 degrees C, the COP will be just over three which means that, for every unit of electrical energy used by the system, it will provide three units of heating energy. 55 degrees C is a typical flow temperature for a low flow temperature radiator system and this is the minimum you must achieve to run a heat pump heating system and get a reasonable COP. Running high temperature radiators is not a viable option for this kind of heating. If the heating is delivered by standard solid floor underfloor heating with a flow temperature of 45 degrees C, then the COP will be closer to 4 and, if you design the underfloor heating to run at a very low temperature of 35 degrees C, then the COP will be nearer to 5. The room will still be at a standard temperature of 21 degrees C, just that the heating flow temperature should be lower.
Another way of improving the performance of a ground source system is to increase the temperature at which the ground circuit returns to the heat pump. I talked earlier about storing energy in the ground and, if you can recharge your ground source circuits with waste heat either from summer cooling or waste solar heating, it is possible to increase the overall performance of the system, sometimes as much a doubling its COP. If you are dumping energy from a high temperature source such as solar though you must ensure that the pipework you use is suitable for the temperature, many are not. Reassuringly, REHAU’s PE-Xa can be used from -40°C to 95°C.
Standards for design of ground source systems can be found in a number of different source including VDI Guidelines 4640: Thermal Use of Underground: Parts 1-4, GSHPA Vertical Borehole Standard, GSHPA Thermal Pile standard and CIBSE Guide TM51 ‘Ground Source Heat Pumps’ released in Feb 2013.
The UK Government’s RHI scheme includes the use of ground source heating and is payable in two tiers. Tier one is 8.6p/kWhrTh for the first 1314 hours of heating and 2.6p/kWhrTh for tier two beyond that. Payment is over 20 years with increases linked to inflation; but all installations must be installed by a MCS accredited installer and it is currently only available for commercial projects. A domestic system is likely to be available in spring 2014 but has not yet been finalised. Interestingly though, a commercial project can be as small as two properties working on one heating system. Most projects will require the use of a class 2 meter to ensure that you can claim your RHI payments from OFGEM.
Energy can be collected from the ground using a variety of different systems. Boreholes can be drilled typically from 80 to 150 m deep and ground source probes (two or four loops of pipe) inserted. Field base systems, where a large area of ground is dug to a depth of 800mm and an array of pipes like underfloor installed, look simple but the amount of soil that needs to be moved can be enormous. Be very careful too if your installer wants to use the so called ‘slinky systems’ where a trench is dug and the trench filled with coils of pipe overlapping each other. This is an ideal environment to encourage ice radii forming at the overlapping of the pipes potentially freezing the ground. A better compromise available from REHAU is ground source spiral probes. Here, a 450mm diameter hole is drilled to 5m deep and the probes inserted in the bottom 3m of the hole, maximising output and minimising costs.
Many commercial projects that are using large diameter structural piles use pipe work fitted inside the pile. Deciding how much energy is available and how you can get it out of the ground is a complex issue. Most commercial projects where a number of boreholes are going to be drilled start by installing a single borehole early in the job. A thermal response test is then carried out where hot water is pumped down the probe and there is a correlation between the heat loss from this hot water and the subsequent amount of energy that can be extracted from the probe. This will require some investment before the job can be designed but it is only when you know the thermal response that you can work out how many boreholes are required on any scheme; and this can have a massive impact on the overall cost. For most domestic jobs, a simple 100m probe is nearly always sufficient. Crude estimates of the local ground’s thermal capacity can be found on www.thermomap-project.eu. This covers most European projects but detailed calculations still need a local thermal response test.
Having installed your boreholes or field based collectors, the systems needs to be connected up to the property and it is here that condensation can be a problem with the water often circulating below freezing. REHAU has a number of specialist products to manage your system with manifold chambers complete with manifolds, insulated header pipe to save the loss of collected energy and a full catalogue of accessories details at: www.rehau.co.uk/groundsource
One final word of warning when letting contracts for ground source heating systems – try to let the contract as a single package for the complete heating system incorporating the ground source, heatpump and internal heating so that nobody can then blame anyone else for failures. REHAU has a range of partners who can offer this service from small domestic projects right through to complex solar recharged ground sources systems.
Mike Moseley is REHAU commercial manager based in their offices in The Building Centre. He is a professional engineer with years of experience in the construction industry. As well as looking after REHAU’s external CPD training converting Introduction to RHI, Ground source heating, Ground Air heat exchanger, District heating and Low energy Fenestration systems, he looks after some of the special projects working on solar storage systems and extracting energy of from tunnels.