Neville Small of Baxi Commercial Division visited on Friday to give the Information Team a briefing on the SOLARflo solar thermal water heating system specially designed for and installed at The Building Centre to meet our water requirements in the most energy efficient way.
The double bank of evacuated tubes installed on a south facing 30 – 40 degree pitched roof has been providing hot water for two kitchens and washroom facilities on three floors since March this year. The system is able to supply up to 40% of the building’s hot water demand and is backed up by an immersion heater within the Megaflo Storage cylinder.
Neville explained the suitability of evacuated tube type solar collectors for our particular installation over flat plate collectors. Flat plate collectors are generally 1 metre by 1.2 metres and with restricted access to our roof it was much easier to install evacuated tubes which could be carried up a few at a time and assembled insitu and connected to the head section containing the manifold.
Neville also demonstrated how each evacuated tube could be angled towards the sun if a perfect south facing elevation was not available for the installation. We saw how shading the tubes had to be avoided to ensure the systems full capacity to generate solar heated water.
It was important to get pipework sizing correct and compression fittings were used to cope with the expansion and contraction caused by the heating and cooling of the liquid being carried in the pipes and to ensure that the storage cylinder was not oversized to prevent stored water cooling to below 60% which would present a risk of legionella. The glycol, which absorbs and carries the heat, needs to be constantly pumped to prevent it from solidifying. If this happens the system would cease to work and would need to be drained down by pressure jet and fresh glycol put in.
We inspected the small plant room housing the cylinder, pump, expansion vessels and smart solar display unit which monitors the amount of heat being generated and gives a cumulative saving from the time of installation. This has been linked to two other units displaying the same information on the Baxi Commercial Product Display on the lower ground floor and on the First Floor, which has been of great interest to visitors. On an overcast day such as last Friday, we saw from the monitor that the system was producing 35 degrees of heat. On a sunny day temperatures of 60 degrees and more have been reached.
It is necessary to have a heat dump to disperse the extra hot water when it is not being used. For a business premises such as ours this would be necessary in very sunny weather on a Sunday or Bank Holiday. Our heat dump takes the form of a radiator which is housed in the plant room. In a residential installation a bathroom towel rail could emit the extra heat which might build up in summer when the occupants are on holiday.
The type of system Baxi have installed for The Building Centre cost around £13,500. The system should last for 25 years and the estimated savings will be £80,000. Pay back time is estimated to be 5 t0 6 years.
Details of the SOLARflo system used, as well as Product Literature can be downloaded and requested here.