Fire doors are now a common part of fire protection specification but simply specifying and purchasing a fire door is only the beginning. A 100% performing fire door includes the installation of the door – a factor that is not being communicated to third party installers, some of whom consciously or unconsciously are installing the doors like an ordinary entrance door. The risk associated with an incorrectly installed fire door is immense, it could cost lives.
Adrian Sunter, sales director for Permadoor, a specialist door supplier to the social housing sector explains the importance of a correct fire door installation, and gives an overview of some of the key elements to look out for.
Survey Specifics
The survey criterion varies dependent on whether it is a new build or a replacement door installation. For a replacement doorset the surveyor is responsible for specifying installation techniques, measuring the aperture and preparing a schedule of any ancillary items including additional hardware. Surveyors should also be fully trained in doorset installation techniques. For a new build the survey details are similar, with specific focus on the product being fitted correctly – square, plumb and without twist. A suitable perimeter clearance should also be allowed for – manufacturing tolerances of the aperture and the doorset.
For fire door installations a deduction should also be taken into consideration. The deduction is 10mm in the width and also for the height, this allows for any fire rated mastic or mortar bed at the cill.
Precision Position
When replacing an existing doorset it is imperative that the new door is installed and sealed on the same day that the old one is removed to ensure continuous fire safety. The positioning of the new frame within the aperture is critical to the success of the installation, the replacement doorset should bridge the cavity, cover the damp proof course and be set back as far as possible in the aperture to minimise exposure to the elements.
All fire doors must also be fitted with a self-closing device capable of returning the door leaf to the latched position.
Fixing Methods
There are two principal methods of fixings available – through-frame and lug. As a general rule only through-frame fixings must be used for fire doorsets.
Through-frame fixings should be plastic sheathed and a minimum of 100mm in length. They should also penetrate a minimum of 50mm into the substrate. The head of any through-frame fixing must be seated beneath the outer wall of the plastic outer frame, within the hollow chamber, to prevent distortion or cracking of the frame. Appropriately sized installation packers should also be used adjacent to the fixing positions; again this prevents the outer frame from distorting during installation. For fire doorsets these packers should be hardwood, or similar material.
Sealing the Perimeter
For a fire door installation the joint widths should never be more than 5mm. Using intumescent mastic the gap should be closed filling the front and back face of the frame to a depth of 15mm. The seal prevents smoke, air and water leakage between the aperture and the doorset. Large and irregular spaces can be locally packed with non combustible mineral fibre to close the gap, with intumescent mastic bead placed over the top.
No One Single Solution
It is unrealistic to think that there is a single solution to fire safety; there’s not a one-size fits all option instead, alongside a risk-based approach, there are some basic, fundamental principles that “…must be applied flexibly to meet the needs of a particular property”, as outlined by the ‘Housing – Fire Safety’ guidance document. Fire doors are an intrinsic principle of this approach, as a complete doorset.
The recommended standard of fire resistance and fire separation is 30 minutes for a normal risk environment. Therefore where fire-resisting partitions are required, any doorway within this must be fitted with a fire door offering the same level of resistance, e.g. 30 minutes or 60 minutes. In most situations, fire doors should also be fitted with smoke seals, this is denoted by the letter ‘S’ after the 30 or 60 figure (denoting the performance time of the doorset in minutes).
Not Just a Door
Fire doors comprise of components which make it perform in the event of a fire, all of which are test certified, this includes the door leaf, frame, seals and hardware. Using the wrong components could have a detrimental impact on the performance of the fire door.
The ‘Housing – Fire Safety’ guidance document continues, “The upgrading of non-fire-resisting door assemblies should be avoided wherever possible. The practice is generally impractical and uneconomic and is reliant upon strict adherence to an approved specification and upon a high standard of workmanship. Replacement with suitable, purpose designed and tested doorset constructions are always preferable.”
This may only be advisory but the message is clear, appropriate use of product is the key to maintaining fire safety. The initial saving associated with upgrading doors over replacement fire doors is a short-term gain, which is soon eroded by the long-term risk – putting lives in danger.
Adrian Sunter is sales director for Permadoor, the original composite door company. As a specialist supplier to the social housing sector, Adrian and his team work closely with local authorities and their contractors and sub-contractors to ensure the accurate specification of a wide range of door products. 2014 see’s Permadoor celebrate its 25th anniversary; with exciting news and developments due to be announced this summer.